Publication detail
An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems
ADZMAN, M. TOPOLÁNEK, D. LEHTONEN, M. TOMAN, P.
Original Title
An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems
Type
journal article - other
Language
English
Original Abstract
This paper proposes a scheme to locate an earth fault in an unearthed or a compensated neutral MV network using the transient signal recorded from MV/LV substations. The algorithm applies CWT to locate the dominant charge transient frequency and then FFT to extract coefficients to be used in the fault location scheme. The fault location scheme managed to identify the correct path of fault location towards the position of the fault using the transient signal recorded from secondary side of the LV substation transformers. The results from intensive simulations and experiments in actual distribution network are also presented in this paper. The final results show that the fault location scheme is able to locate and identify the correct fault location successfully.
Keywords
Charge transient; Compensated network; Continuous wavelet transform (CWT); Earth fault; Fault location; Isolated neutral network; Low voltage secondary substation
Authors
ADZMAN, M.; TOPOLÁNEK, D.; LEHTONEN, M.; TOMAN, P.
RIV year
2013
Released
1. 10. 2013
Publisher
Federico II University
Location
21 Claudio - I80125 Naples, Italy
ISBN
1827-6660
Periodical
International Review of Electrical Engineering (IREE)
Year of study
8
Number
5
State
Republic of Italy
Pages from
1520
Pages to
1531
Pages count
12
BibTex
@article{BUT102664,
author="Mohd Rafi {Adzman} and David {Topolánek} and Matti {Lehtonen} and Petr {Toman}",
title="An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems",
journal="International Review of Electrical Engineering (IREE)",
year="2013",
volume="8",
number="5",
pages="1520--1531",
issn="1827-6660"
}