Detail publikace
An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems
ADZMAN, M. TOPOLÁNEK, D. LEHTONEN, M. TOMAN, P.
Originální název
An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems
Typ
článek v časopise - ostatní, Jost
Jazyk
angličtina
Originální abstrakt
This paper proposes a scheme to locate an earth fault in an unearthed or a compensated neutral MV network using the transient signal recorded from MV/LV substations. The algorithm applies CWT to locate the dominant charge transient frequency and then FFT to extract coefficients to be used in the fault location scheme. The fault location scheme managed to identify the correct path of fault location towards the position of the fault using the transient signal recorded from secondary side of the LV substation transformers. The results from intensive simulations and experiments in actual distribution network are also presented in this paper. The final results show that the fault location scheme is able to locate and identify the correct fault location successfully.
Klíčová slova
Charge transient; Compensated network; Continuous wavelet transform (CWT); Earth fault; Fault location; Isolated neutral network; Low voltage secondary substation
Autoři
ADZMAN, M.; TOPOLÁNEK, D.; LEHTONEN, M.; TOMAN, P.
Rok RIV
2013
Vydáno
1. 10. 2013
Nakladatel
Federico II University
Místo
21 Claudio - I80125 Naples, Italy
ISSN
1827-6660
Periodikum
International Review of Electrical Engineering (IREE)
Ročník
8
Číslo
5
Stát
Italská republika
Strany od
1520
Strany do
1531
Strany počet
12
BibTex
@article{BUT102664,
author="Mohd Rafi {Adzman} and David {Topolánek} and Matti {Lehtonen} and Petr {Toman}",
title="An Earth Fault Location Scheme For Isolated and Compensated Neutral Distribution Systems",
journal="International Review of Electrical Engineering (IREE)",
year="2013",
volume="8",
number="5",
pages="1520--1531",
issn="1827-6660"
}