Practical Experience of Using Additional Earthing of the Faulty Phase During a Ground Fault
TOPOLÁNEK, D. TOMAN, P. ORSÁGOVÁ, J. DVOŘÁK, J.
Originální název
Practical Experience of Using Additional Earthing of the Faulty Phase During a Ground Fault
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
The paper is focused on the operational experience with an automatic system for suppression of a fault current during a ground fault by the additional earthing of the faulted phase in a supply substation. Such system was experimentally installed in the Brno-Medlánky 110/22 kV substation. To verify the benefits of the system as well as to assess its possible failings, twenty-four experimental measurements based on a theoretical study were performed. During those experiments, low-resistance and arc ground faults were monitored in the urban and suburban part of the compensated network with a capacitive current of 300 A and 800 A. The results of the crucial experiments and the evaluation of the system functioning are summed up in the final part of the paper.
Klíčová slova
ground fault, compensated, distribution network, earthing, shunt, residual current, faulty current, capacitive current
Autoři
TOPOLÁNEK, D.; TOMAN, P.; ORSÁGOVÁ, J.; DVOŘÁK, J.
Rok RIV
2013
Vydáno
16. 6. 2013
Nakladatel
IEEE
Místo
Grenoble (France)
ISBN
978-1-4673-5667-1
Kniha
Ieee Proceedings Power Tech 2013
Strany od
1
Strany do
6
Strany počet
6
BibTex
@inproceedings{BUT100322,
author="David {Topolánek} and Petr {Toman} and Jaroslava {Orságová} and Jaromír {Dvořák}",
title="Practical Experience of Using Additional Earthing of the Faulty Phase During a Ground Fault",
booktitle="Ieee Proceedings Power Tech 2013",
year="2013",
pages="1--6",
publisher="IEEE",
address="Grenoble (France)",
doi="10.1109/PTC.2013.6652291",
isbn="978-1-4673-5667-1"
}